Recall date: March 31, 2016
Recall number: 16-134
Enlarge
-
1 of 3 photos
Fire Alarm Panel
-
2 of 3 photos
ILI-MB-E3-KINETIS Panel
-
3 of 3 photos
ILI-S-E3-KINETIS Panel
Recall Summary
Name of product: Gamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3)
Hazard:
When configured in a certain way, the panels can become non-responsive and connected detectors in the area can fail to detect and respond to an alarm.
Consumer Contact:
Gamewell-FCI at 800-274-4324 from 7 a.m. to 7 p.m. ET Monday through Friday or online at
www.gamewell-fci.com and click on “Safety Recall” for more information.
Report an Incident Involving this Product
Recall Details
Units
About 1,000
Description
This recall is for the ILI-MB-E3 and ILI-S-E3 Gamewell-FCI fire alarm panels in commercial buildings. This issue is limited to a specific configuration of Signaling Line Circuit (SLC) devices. To occur, the SLC must include at least two of the following detectors in any combination: Acclimate, 4-Warn, Photo/CO and iFAAST. The issue would occur only if the detectors are addressed within the same FlashScan polling group. Detectors installed in a different combination are not affected.
Incidents/Injuries
No incidents or injuries have been reported.
Remedy
Consumers should immediately contact the distributor to obtain the free repair, a firmware upgrade.
Sold at
Authorized distributors from May 2015 through August 2015 for about $800.
Importer(s)
Gamewell-FCI of Northford, Conn.
Manufactured in
U.S.